Model
MBRL 802 T4 22kW
Code
501608055

MBRL 802 T4 22kW

MEDIUM PRESSURE WITH BACKWARD IMPELLER

MANUFACTURING FEATURES:

• Fan made of Fe360 sheet. The fan paint finish is based on a Qualicoat polyester powder coating stoved at 200ºC, with an average film thickness of 70 microns. Average heat resistence of coating is 180ºC with peaks of 200ºC.
• Fully welded or joined housing.
• Simple inlet backward impeller with self-cleaning system made of Fe360 sheet statically and dynamically balanced.
Impellers are painted with polyester primer that resists temperatures up to 300ºC.
• Standard asynchronous squirrel-cage motor with IP-55 protection and class F insulation. Manufactured with standard voltages: 230/400V 50Hz in single phase motors and 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.
• Standard orientation LG270.
• It allows adjusting the orientation locally from models 250 to 630. Models sizes from 710 to 1400 size the orientation is fixed.

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Clean and slightly dusty air transport.
• Exhaust after filters, separators and cyclones.
• Pneumatic transport.
• Maximum working temperature: carried air: 130ºC, ambient: 60ºC.

UNDER REQUEST:

• 60Hz fans and special voltages.
• 2 speed motors.
• Spark-proof fans with ATEX certified motor. 
• Fan for air working temperatures up to 250ºC with R/R (cooling impeller).
• Hot-dipped galvanised or stainless steel fans.
• Orientation: RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315, LG0, LG45, LG90, LG135, LG180. LG225, LG315.

Fan

Max flow
36010 m³/h
Weight
484 Kg

Motor

Power
22 kW
RPM Motor
1465
I max. 400 V
40,1
I max. 690 V
23,2
Size
180L
Weight
185 Kg
Efficiency
93 %
FP
0.86
MBRL 802 T4 22kW
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

MBRL 802 T4 22kW

Dimensions scheme
a A a1 a2 b B b1 b2 C d D d1 D1 d2 D2 D3 D4 D5 D6 D7 E F G H H1 H2 I J K L M N N1xØ1 n1xp N2xØ2 n2xp O O6 Ø3 P R S S1 S2 S3 S4 S5 S6 S7 T U W X X1 X2 X3 X4 X5 X6 X7
801 287 871 921 569 1239 639 689 1342 805 560 861 939 905 811 782 749 652 562 1061 1602 478 285 950 630 950 361 862 926 932 463 570 16x14 2x200 14x14 3x200 60 501 19 862 39 782 652 562 560 1061 939 811 749 27 1095 668 652 560 1061 939 811 782 749 562

MBRL 802 T4 22kW

Electrical scheme

MBRL 802 T4 22kW

Model
AC 800
Code
960003218
Information
CONECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
JE 45
Code
300719201
Information
ANTI-VIBRATION JOINT

MANUFACTURING FEATURES

• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.

Model
RA 805x16
Code
510008000
Information
INLET PROTECTION GUARD FOR CENTRIFUGAL FANS

MANUFACTURING FRATURES

• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of galvanised steel models 7,9, 10, 12 and 15. And the rest of models with polyester powder finishing coat.

Model
RI 801x569
Code
510108000
Information
OUTLET PROTECTION GUARD FOR FANS

MANUFACTURING FRATURES

• Galvanized protection grid on the outlet side to avoid the entry of objects and contact with the impeller.

Model
EI 801x569-800
Code
510208002
Information
CIRCULAR OUTLET CONNECTION FLANGE

MANUFACTURING FEATURES

• Connection to be fitted in the centrifugal fans outlet.
• Manufactured in galvanized steel.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
INT 63 3P A
Code
INT633PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
SFC 400 III 45A **
Code
SFC400III45
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

MBRL 802 T4 22kW

Spare parts scheme
Code Family Name Qty
2 T01608055 TURBINE MBRL 802 T4 22kW LG x1
3 503408000SP04 INLET CONE MBRL/MTRL 800 x1
4 721001195 MOTOR 22KW T4 B3 400/690V x1